Rockwell Automation 294E ArmorStart LT EtherNet/IP Version - User Manual User Manual
Page 154

154
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 4
Bulletin 290E/291E/294E Programmable Parameters
Figure 56 - Boost Select
MaximumVoltage
Sets the highest voltage the drive will output.
Parameter Number
87
Related Parameters
—
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Config.
Units
V AC
Minimum Value
20V AC
Maximum Value
460V AC
Default Value
2V AC
MotorNamePlateFLA
Set to the motor nameplate Full Load Amps.
For 0.5 Hp units – Min = 0; Max = 3.0; Default = 1.5
For 1.0 Hp units – Min = 0; Max = 5.0; Default = 2.5
For 2.0Hp units – Min = 0; Max = 8.4; Default = 3.6
Parameter Number
88
Related Parameters
—
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Config.
Units
x.x Amps
Minimum Value
0.0
Maximum Value
Hp Dependent
Default Value
Hp Dependent
1/2 [Motor NP Volts]
%P28 [Mot
or NP
Volts]
%P29 [Motor NP Hertz]
[Mot
or NP Her
tz]
1/2
0
50
100
100
50
Settings
5-14
4
3
2
1