Rockwell Automation 294E ArmorStart LT EtherNet/IP Version - User Manual User Manual

Page 122

background image

122

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Chapter 4

Bulletin 290E/291E/294E Programmable Parameters

JamWarningLevel

This parameter determines the Jam
Warning Level as a percentage
of Full Load Amps.

Parameter Number

73

Access Rule

GET

Data Type

UINT

Group

Advanced Config.

Units

%FLA

Minimum Value

50

Maximum Value

600

Default Value

150

StallEnabledTime

This parameter determines the time
that stall detection is enabled during
motor starting.

Parameter Number

74

Access Rule

GET

Data Type

USINT

Group

Advanced Config.

Units

secs

Minimum Value

0

Maximum Value

250

Default Value

10

StallTripLevel

This parameter determines the Stall Trip
Level as a percentage of Full Load Amps.

Parameter Number

75

Access Rule

GET

Data Type

UINT

Group

Advanced Config.

Units

%FLA

Minimum Value

100

Maximum Value

600

Default Value

600

ULInhibitTime

This parameter determines the time
during motor starting that Underload
detection is inhibited.

Parameter Number

76

Access Rule

GET

Data Type

USINT

Group

Advanced Config.

Units

secs

Minimum Value

0

Maximum Value

250

Default Value

10