Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

147

Bulletin 290E/291E/294E Programmable Parameters Chapter 4

MotorOLRetention

Enables/disables the Motor overload
Retention function. When Enabled, the
value held in the motor overload counter
is saved at power-down and restored
at power-up. A change to this parameter
setting resets the counter.
0 = Disabled (Default)
1 = Enabled

Parameter Number

71

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

InternalFreq

Provide the frequency command to drive
when Parameter 33 (Speed-Reference) =
1 (InternalFreq). When enabled, this
parameter will change the frequency
command in real time.

Parameter Number

72

Related Parameters

33

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Config.

Units

x.x Hz

Minimum Value

0.0

Maximum Value

400.0

Default Value

60.0

SkipFrequency

Sets the frequency at which the drive will
not operate.

Parameter Number

73

Related Parameters

74

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Config.

Units

Hz

Minimum Value

0

Maximum Value

400 Hz

Default Value

0 Hz

SkipFrqBand

Determines the band width around
Parameter 73 (SkipFrequency). Parameter
74 (SkipFreqBand) is split applying 1/2
above and 1/2 below the actual skip
frequency. A setting of 0.0 disables
this parameter.

Parameter Number

74

Related Parameters

73

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Config.

Units

x.x Hz

Minimum Value

0.0 Hz

Maximum Value

30.0 Hz

Default Value

0.0 Hz