Bulletin 290E/291E/294E Programmable Parameters Chapter 4

Speed Control Group

SpeedReference

Sets the source of the speed reference:
0 = Logix (Network or DeviceLogix)
1 = InternalFreq

Parameter Number

33

Related Parameters

1, 2, 36, 37, 72

Access Rule

GET/SET

Data Type

UINT

Group

Speed Control

Units

Minimum Value

0

Maximum Value

2

Default Value

0

MinimumFreq

Sets the lowest frequency the drive will
output continuously.

Parameter Number

34

Related Parameter

1, 2, 35

Access Rule

GET/SET

Data Type

UINT

Group

Speed Control

Units

x.x Hz

Minimum Value

0.0

Maximum Value

400.0

Default Value

0.0

MaximumFreq

Sets the highest frequency the drive will
output.

Parameter Number

35

Related Parameter

1, 2, 34, 35, 139

Access Rule

GET/SET

Data Type

UINT

Group

Speed Control

Units

Hz

Minimum Value

0.0

Maximum Value

400

Default Value

60

Stop drive before changing this
parameter.