Bulletin 290E/291E/294E Programmable Parameters

Advanced Configuration

SetToDefaults

This parameter if set to “1” will set the
device to the factory defaults.
0 = NoAction
1 = SetToDefaults

Parameter Number

68

Access Rule

GET/SET

Data Type

BOOL

Group

Misc. Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

AccelTime2

When active, sets the rate of acceleration for all speed increases except for jog.

Parameter Number

69

Related Parameters

36

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Config.

Units

x.x secs

Minimum Value

0.0

Maximum Value

600.0

Default Value

20.0

Maximum Freq

Accel Time

--------------------------------------

Accel Rate

=

Parameter 35

(Maximum Freq)

Speed

Accel

Time 2

0

0

Time

Decel

Time 2

Acc

eler

ation

Dec

eler

ation

DecelTime2

When active, sets the rate of deceleration for all speed decreases except for jog.

Parameter Number

70

Related Parameters

37

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Config.

Units

x.x secs

Minimum Value

0.0

Maximum Value

600.0

Default Value

20.0

Maximum Freq

Decel Time

--------------------------------------

Decel Rate

=

Parameter 35

(Maximum Freq)

Speed

Accel

Time 2

0

0

Time

Decel

Time 2

Acc

eler

ation

Dec

eler

ation