beautypg.com

Armorconnect cable ratings – Rockwell Automation 294E ArmorStart LT EtherNet/IP Version - User Manual User Manual

Page 49

background image

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

49

Installation and Wiring

Chapter 2

6. The E-stop Out tee (Cat. No.: 898N-653ES-NKF) is used with cordset or patchcord to connect to the ArmorStart Distributed Motor Controller.

7. Control Power Receptacles – Female receptacles are a panel mount connector with flying leads (Cat. No.: 888N-D65AF1-*)

8. Three-Phase Power Trunk – Patchcord cable with integral female or male connector on each end (Example Cat. No.:280-PWRM35A-M*)

9. Three-Phase Drop Cable – PatchCord cable with integral female or male connector on each end (Example Cat. No.:280-PWRM22A-M*)

10. Three-Phase Power Tees and Reducer – Tee connects to a single drop line to trunk with quick change connectors (Cat. No.: 280-T35)

Reducing Tee connects to a single drop line (Mini) to trunk (Quick change) connector (Cat. No.: 280-RT35)
Reducer connects from quick change male connector to mini female connector (Cat. No.: 280-RA35)

11. Three-Phase Power Receptacles – Female receptacles are a panel mount connector with flying leads (Cat. No.: 280-M35F-M1)

Figure 24 - On-Machine Stop Stations

ArmorConnect Cable Ratings

The ArmorConnect Power Media cables are rated per UL Type TC 600V 90°C
Dry 75°C Wet, Exposed Run (ER) or MTW 600V 90°C or STOOW 105°C
600V - Canadian Standards Association (CSA) STOOW 600V FT2.
For additional information regarding ArmorConnect Power Media refer
to ArmorStart LT selection guide, publication 290-SG001_-EN-P.

Branch Circuit Protection Requirements for ArmorConnect
Three-Phase Power Media

When using ArmorConnect Three-Phase Power Media, fuses or circuit breakers
may be used for the motor branch circuit ground fault protection if properly
sized and allowed by product labeling.

Circuit Breaker:

Where ArmorStart LT is used with ArmorConnect — suitable for use on a
circuit capable of delivering not more than 10000 RMS Symmetrical Amperes

IMPORTANT

See the On-Machine Connectivity catalog for specific Ethernet
media components

Enclosure

Type

Quick Connect

Knockout

Type

Operator

Illumination

Voltage

Contact

Configuration

Cat. No.

Plastic

Mini Receptacle

Metric

Twist to Release

24V AC/DC

1 N.C./1 N.O.

800F-1YMQ4

Metal

24V AC/DC

800F-1MYMQ4