Rockwell Automation 294E ArmorStart LT EtherNet/IP Version - User Manual User Manual
Page 139
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
139
Bulletin 290E/291E/294E Programmable Parameters Chapter 4
WarningEnable
This parameter enables a warning
by setting the bit to 1.
Parameter Number
43
Access Rule
GET/SET
Data Type
WORD
Group
Starter Protection
Units
—
Minimum Value
0
Maximum Value
0xC044
Default Value
0
Bit
Function
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
— — — — — — — — — — — — — —
X
X
Reserved
— — — — — — — — — — — — —
X
— —
UnderPowerWarn
— — — — — — — — — —
X
X
X
— — —
Reserved
— — — — — — — — —
X
— — — — — —
DriveParamInit
— —
X
X
X
X
X
X
X
— — — — — — —
Reserved
—
X
— — — — — — — — — — — — — —
UnswitchedPwrWarn
X
— — — — — — — — — — — — — — —
ConfigWarning
ProtectFltReset
This parameter resets a Protection Fault
by setting the bit to 1.
0 = NoAction
0 > 1 = ResetFault
Parameter Number
44
Access Rule
GET/SET
Data Type
BOOL
Group
Starter Protection
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
RunNetFltAction
This parameter in conjunction with
Parameter 46 (RunNetFltValue) defines
how the starter will respond when a
network fault occurs as determined.
0 = GoToFaultValue
1 = HoldLastState
Parameter Number
45
Access Rule
GET/SET
Data Type
BOOL
Group
Starter Protection
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0