Rockwell Automation 294E ArmorStart LT EtherNet/IP Version - User Manual User Manual

Page 139

background image

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

139

Bulletin 290E/291E/294E Programmable Parameters Chapter 4

WarningEnable

This parameter enables a warning
by setting the bit to 1.

Parameter Number

43

Access Rule

GET/SET

Data Type

WORD

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

0xC044

Default Value

0

Bit

Function

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

— — — — — — — — — — — — — —

X

X

Reserved

— — — — — — — — — — — — —

X

— —

UnderPowerWarn

— — — — — — — — — —

X

X

X

— — —

Reserved

— — — — — — — — —

X

— — — — — —

DriveParamInit

— —

X

X

X

X

X

X

X

— — — — — — —

Reserved

X

— — — — — — — — — — — — — —

UnswitchedPwrWarn

X

— — — — — — — — — — — — — — —

ConfigWarning

ProtectFltReset

This parameter resets a Protection Fault
by setting the bit to 1.
0 = NoAction
0 > 1 = ResetFault

Parameter Number

44

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

RunNetFltAction

This parameter in conjunction with
Parameter 46 (RunNetFltValue) defines
how the starter will respond when a
network fault occurs as determined.
0 = GoToFaultValue
1 = HoldLastState

Parameter Number

45

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0