Rockwell Automation 294E ArmorStart LT EtherNet/IP Version - User Manual User Manual
Page 123

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
123
Bulletin 290E/291E/294E Programmable Parameters Chapter 4
ULTripDelay
This parameter determines the time below
Underload Level before the unit will trip.
Parameter Number
77
Access Rule
GET
Data Type
USINT
Group
Advanced Config.
Units
x.x secs
Minimum Value
1
Maximum Value
25.0
Default Value
5.0
ULTripLevel
This parameter determines the
Underload Trip Level as a percentage
of Full Load Amps.
Parameter Number
78
Access Rule
GET
Data Type
USINT
Group
Advanced Config.
Units
%FLA
Minimum Value
10
Maximum Value
100
Default Value
50
ULWarningLevel
This parameter determines the
Underload Warning Level as a
percentage of Full Load Amps.
Parameter Number
79
Access Rule
GET
Data Type
USINT
Group
Advanced Config.
Units
%FLA
Minimum Value
10
Maximum Value
100
Default Value
70