Bulletin 290E/291E/294E Programmable Parameters Chapter 4

ULTripDelay

This parameter determines the time below
Underload Level before the unit will trip.

Parameter Number

77

Access Rule

GET

Data Type

USINT

Group

Advanced Config.

Units

x.x secs

Minimum Value

1

Maximum Value

25.0

Default Value

5.0

ULTripLevel

This parameter determines the
Underload Trip Level as a percentage
of Full Load Amps.

Parameter Number

78

Access Rule

GET

Data Type

USINT

Group

Advanced Config.

Units

%FLA

Minimum Value

10

Maximum Value

100

Default Value

50

ULWarningLevel

This parameter determines the
Underload Warning Level as a
percentage of Full Load Amps.

Parameter Number

79

Access Rule

GET

Data Type

USINT

Group

Advanced Config.

Units

%FLA

Minimum Value

10

Maximum Value

100

Default Value

70