Page 102: Bulletin 290e/291e, Basic status group

background image

102

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Chapter 4

Bulletin 290E/291E/294E Programmable Parameters

ArmorStart LT EtherNet/IP
Parameters

Introduction

This chapter describes each programmable parameter and its function.

Parameter Programming

Each Distributed Motor Controller type will have a common set of parameters
and a set of parameters that pertain to the individual starter type. Parameters
41

68 are common to all ArmorStart LTs.

Bulletin 290E/291E

Basic Status Group

IMPORTANT

Parameter setting changes take effect immediately unless otherwise noted
in the parameter listing. These changes maybe immediate even during the
"running" status.

PhaseL1Current

This parameter determines the actual
Phase L1 current.

Parameter Number

1

Access Rule

GET

Data Type

INT

Group

Basic Status

Units

x.xx Amps

Minimum Value

0

Maximum Value

32767

Default Value

0

PhaseL2Current

This parameter determines the actual
Phase L2 current.

Parameter Number

2

Access Rule

GET

Data Type

INT

Group

Basic Status

Units

x.xx Amps

Minimum Value

0

Maximum Value

32767

Default Value

0