148

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Chapter 4

Bulletin 290E/291E/294E Programmable Parameters

Figure 54 - Skip Frequency Band

DCBrakeTime

Sets the length of time that DC brake current is
injected into the motor. Refer to Parameter 76
(DCBrakeLevel).

Parameter Number

75

Related Parameters

32, 76

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Config.

Units

x.x secs

Minimum Value

0.0

Maximum Value

99.9

(Setting of 99.9 = Continuous)

Default Value

0.0

DCBrakeLevel

Defines the maximum DC brake current, in amps,
applied to the motor when Parameter 32
(StopMode) is set to either
0 = RAMP or 2 = DC BRAKE.

For 0.5 Hp units – Min = 0; Max = 2.7; Default = .1
For 1.0 Hp units – Min = 0; Max = 4.5; Default = .1
For 2.0Hp units – Min = 0; Max = 7.5; Default = .2

Parameter Number

76

Related Parameters

32, 75

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Config.

Units

x.x Amps

Minimum Value

0.0

Maximum Value

Hp Dependant

Default Value

Hp Dependant

Frequency

Time

Skip Frequency

Command

Frequency

Drive Output

Frequency

2x Skip

Frequency Band