beautypg.com

Overload object, Class code 0x002c – Rockwell Automation 294E ArmorStart LT EtherNet/IP Version - User Manual User Manual

Page 216

background image

216

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Appendix B

CIP Information

➊ Reversing Starters (291E) and Inverter (294E) Starters only

The following common services will be implemented for the Control Supervisor
Object.

Overload Object

CLASS CODE 0x002C

No class attributes will be supported for the Overload Object.

A single instance (Instance 1) of the Overload Object is supported for DOL
(Bulletin 290E/291E) and Reversing (Bulletin 294E) Starters. Instance 1
contains the following instance attributes.

Attribute ID

Access Rule

Name

Data Type

Value

3

Get/Set

Run 1

BOOL

These Run outputs also map to DOP Instances 1 and 2

4

Get/Set

Run 2

BOOL

7

Get

Running 1

BOOL

8

Get

Running 2

BOOL

9

Get

Ready

BOOL

10

Get

Tripped

BOOL

12

Get/Set

Fault Reset

BOOL

0 > 1 = Trip Reset

Service Code

Implemented for:

Service Name

Class Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

Attribute ID

Access Rule

Name

Data Type

Value

3

Get/Set

FLA Setting

BOOL

xxx.x amps

4

Get/Set

Trip Class

USINT

5

Get

Average Current

INT

xxx.x amps

7

Get

% Thermal Utilized

USINT

xxx% FLA

8

Get

Current L1

INT

xxx.x Amps

9

Get

Current L2

INT

10

Get

Current L3

INT

190

Get/Set

FLA Setting Times 10

BOOL

xxx.xx Amps

192

Get

Average Current Times 10

UINT

193

Get

Current L1 Times 10

UINT

194

Get

Current L2 Times 10

UINT

195

Get

Current L3 Times 10

UINT