Shielded cable, Recommended cable connectors/glands – Rockwell Automation 294E ArmorStart LT EtherNet/IP Version - User Manual User Manual
Page 60
![background image](/manuals/577727/60/background.png)
60
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 2
Installation and Wiring
Figure 34 - Unshielded Multi-Conductor Cable
Shielded Cable
Shielded cable contains all of the general benefits of multi-conductor cable
with the added benefit of a copper braided shield that can contain much
of the noise generated by a typical AC Drive. Strong consideration for shielded
cable should be given for installations with sensitive equipment such as weigh
scales, capacitive proximity switches, and other devices that may be affected
by electrical noise in the distribution system. Applications with large numbers
of drives in a similar location, imposed EMC regulations, or a high degree
of communications/networking are also good candidates for shielded cable.
An acceptable shielded cable will have 4 XLPE insulated conductors with a
100% coverage foil and an 85% coverage copper braided shield (with drain wire)
surrounded by a PVC jacket.
Figure 35 - Shielded Cable with Four Conductors
Recommended Cable Connectors/Glands
Choose cable connectors or glands that offer the best cable protection, shield
termination, and ground contact.
G
R
B
W
Filler
PVC Outer
Sheath
Single Ground
Conductor
B
R
G
W
Shield
Drain Wire