Bulletin 290E/291E/294E Programmable Parameters Chapter 4

Advanced Configuration

OLWarningLevel

This parameter determines the Overload
Warning Level in % Thermal Capacity Used
(%TCU).

Parameter Number

69

Access Rule

GET

Data Type

USINT

Group

Advanced Config.

Units

%TCU

Minimum Value

0

Maximum Value

100

Default Value

85

JamInhibitTime

This parameter determines the time
during motor starting that Jam detection
is inhibited.

Parameter Number

70

Access Rule

GET

Data Type

USINT

Group

Advanced Config.

Units

secs.

Minimum Value

0

Maximum Value

250

Default Value

10

JamTripDelay

This parameter determines how much
time above the Jam Level before the unit
will trip.

Parameter Number

71

Access Rule

GET

Data Type

USINT

Group

Advanced Config.

Units

x.x secs

Minimum Value

1

Maximum Value

25.0

Default Value

5.0

JamTripLevel

This parameter determines the Jam Trip
Level as a percentage of Full Load Amps.

Parameter Number

72

Access Rule

GET

Data Type

UINT

Group

Advanced Config.

Units

%FLA

Minimum Value

50

Maximum Value

600

Default Value

250