Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Chapter 4

Bulletin 290E/291E/294E Programmable Parameters

User I/O Configuration Group

RunNetFltValue

This parameter determines how the starter
will be commanded in the event of a fault.
State the starter will go to on a NetFlt if
Parameter 45 (RunNetFltAction) = 1
(GotoFault-Value).
0 = OFF
1 = ON

Parameter Number

46

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

RunNetIdlAction

This parameter in conjunction with
Parameter 48 (RunNetIdlValue) defines
how the starter will respond when
a network is idle as determined
by Parameter 48.
0 = GoToIdleValue
1 = HoldLastState

Parameter Number

47

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

RunNetIdlValue

This parameter determines the state that
starter assumes when the network is idle
and Parameter 47 (RunNetIdlAction) is
set to 1.
0 = OFF
1 = ON

Parameter Number

48

Access Rule

GET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

0x3F

Default Value

0

IOPointConfigure

This parameter determines the point
that is configured:
0 = Input
1 = Output

Parameter Number

49

Access Rule

GET/SET

Data Type

WORD

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

0x3F

Default Value

0