Analog input point object, Analog output point object – Rockwell Automation 294E ArmorStart LT EtherNet/IP Version - User Manual User Manual
Page 211
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
211
CIP Information
Appendix B
Analog Input Point Object
CLASS CODE 0x000A (Implemented in Bulletin 294E units only)
The following class attributes will be supported for the Analog Input Point
Object:
One instance of the Analog Input Point Object will supported. CommandFreq
from Assembly 154 is placed in the value attribute when it is consumed.
The following common services will be implemented for the Analog Input Point
Object:
Analog Output Point Object
CLASS CODE 0x000B (Implemented in Bulletin 294E units only)
The following class attributes will be supported for the Analog Output Point
Object:
One instance of the Analog Output Point object will supported. It will represent
the Frequency command sent to the PF40 via the DSI link. CommandFreq from
Assembly 154 is placed in the Value Attribute when it is consumed. The Value
Attribute can then be overwritten by DeviceLogix.
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
UINT
2
2
Get
Max Instance
UINT
1
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Value
INT
0 = Default
Service Code
Implemented for:
Service Name
Class Instance
0x0E Yes
Yes
Get_Attribute_Single
0x10 No
Yes
Set_Attribute_Single
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
UINT
2
2
Get
Max Instance
UINT
1
Attribute ID
Access Rule
Name
Data Type
Value
3
Get/Set
Value
INT
0 = Default
129
Get/Set
Input Binding
STRUCT:
USINT
Array of USINT
Size of Appendix I encoded path
Appendix I encoded path
NULL path means attribute 3 drives the output.
Otherwise, this is a path to a bit in the Bit Table.