CIP Information

Appendix B

Four instances of the DPI Fault Object will be supported.

The following common services will be implemented for the DPI Fault Object.

The table below lists Fault Codes, Fault Text, and Fault Help Strings for DOL
and Reversers.

Attribute ID

Access Rule

Name

Data Type

Value

0

Get

Full/All Info

Fault Code
Fault Source

DPI Port Number
Device Object Instance

Fault Text
Fault Time Stamp

Timer Value
Timer Descriptor

Help Object Instance
Fault Data

Struct of:

UINT
Struct of:

USINT
USINT

BYTE [16]
Struct of:

ULDINT
WORD

USINT

Array [5] of 32 bit fault data
values

See Tables below

0

See Tables below

Snapshot data

1

Get

Basic Info

Fault Code
Fault Source

DPI Port Number
Device Object Instance

Fault Time Stamp

Timer Value
Timer Descriptor

Struct of:

UINT
Struct of:

USINT
USINT

Struct of:

ULINT
WORD

See Tables below

0

3

Get

Help Text

STRING

See Tables below

Service Code

Implemented for:

Service Name

Class Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

Yes

No

Set_Attribute_Single

Table 33 - Fault Codes, Fault Text, and Fault Help Strings for DOL and Reversers

Fault

Code

Fault Text

Help Text

1

Fault 1

2

User Defined

User defined trip has occurred.

3

Overload Trip

Load has drawn excessive current based on trip class selected.

4

Fault 4

5

Phase Loss Trip

Indicates missing supply phase. This fault can be disabled.

6

Jam Trip

Motor current above jam level for more than jam trip delay time.

7

Underload Trip

Motor current below UL level for more than UL trip delay time.

8

Fault 8

9

Fault 9

10

Fault 10

11

Fault 11

12

Stall Trip

Motor current above stall trip level during motor starting.

13

Switched Power

Indicates the loss of switched control power.

Not available in units with Integrated Power Supply.