Rockwell Automation 294E ArmorStart LT EtherNet/IP Version - User Manual User Manual
Page 219

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
219
CIP Information
Appendix B
Four instances of the DPI Fault Object will be supported.
The following common services will be implemented for the DPI Fault Object.
The table below lists Fault Codes, Fault Text, and Fault Help Strings for DOL
and Reversers.
Attribute ID
Access Rule
Name
Data Type
Value
0
Get
Full/All Info
Fault Code
Fault Source
DPI Port Number
Device Object Instance
Fault Text
Fault Time Stamp
Timer Value
Timer Descriptor
Help Object Instance
Fault Data
Struct of:
UINT
Struct of:
USINT
USINT
BYTE [16]
Struct of:
ULDINT
WORD
USINT
Array [5] of 32 bit fault data
values
See Tables below
0
See Tables below
Snapshot data
1
Get
Basic Info
Fault Code
Fault Source
DPI Port Number
Device Object Instance
Fault Time Stamp
Timer Value
Timer Descriptor
Struct of:
UINT
Struct of:
USINT
USINT
Struct of:
ULINT
WORD
See Tables below
0
3
Get
Help Text
STRING
See Tables below
Service Code
Implemented for:
Service Name
Class Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
Yes
No
Set_Attribute_Single
Table 33 - Fault Codes, Fault Text, and Fault Help Strings for DOL and Reversers
Fault
Code
Fault Text
Help Text
1
Fault 1
—
2
User Defined
User defined trip has occurred.
3
Overload Trip
Load has drawn excessive current based on trip class selected.
4
Fault 4
—
5
Phase Loss Trip
Indicates missing supply phase. This fault can be disabled.
6
Jam Trip
Motor current above jam level for more than jam trip delay time.
7
Underload Trip
Motor current below UL level for more than UL trip delay time.
8
Fault 8
—
9
Fault 9
—
10
Fault 10
—
11
Fault 11
—
12
Stall Trip
Motor current above stall trip level during motor starting.
13
Switched Power
Indicates the loss of switched control power.
Not available in units with Integrated Power Supply.