Branch circuit protection, Table 8 – Rockwell Automation 294E ArmorStart LT EtherNet/IP Version - User Manual User Manual
Page 46
46
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 2
Installation and Wiring
Table 8 - Power, Control, and Ground Wire Capacity and the Tightening Torque Requirements
Branch Circuit Protection
The ArmorStart LT is Underwriters Laboratory (UL) Group Motor listed. Refer
to the product
for maximum branch fuse and circuit
breaker ratings. Select the motor branch circuit protection device that complies
with NFPA70 (NEC) or NFPA79, and any other governing regional or local
codes. The installer shall observe the product nameplate markings and not apply
the ArmorStart LT where the maximum perspective short circuit current is
exceeded. The ArmorStart LT shall be applied to a solidly grounded WYE power
distribution system that does not exceed 480V AC, 60 Hz or 400V AC, 50 Hz.
Power Terminals
Wire Size
(2) #18…#10 AWG (0.8…5.2 mm
2
) per terminal
Tightening Torque
10.6 +/– 2 lb•in (1.2 +/– 0.2 N•m)
Motor Terminals
Wire Size
#18…#10 AWG (0.8…5.2 mm
2
) per terminal
Tightening Torque
10.6 +/– 2 lb•in (1.2 +/– 0.2 N•m)
Control Terminals
Wire Size
(2) #18…#10 AWG (0.8…5.2 mm
2
) per terminal
Tightening Torque
10.6 +/– 2 lb•in (1.2 +/– 0.2 N•m)
PE/Ground
Wire Size
(2) #16…#10 AWG (1.3…5.2 mm
2
) per terminal
Tightening Torque
18 +/– 2 lb•in (2 +/– 0.2 N•m)
Source Brake (Bulletin 294)
Wire Size
#16 …#10 AWG (1.0…4.0 mm
2
) per terminal
Tightening Torque
4.8 ± 2 lb•in (0.5 ± 0.2 N•m )
IMPORTANT
ArmorStart LT is UL Listed for use with 14 AWG wire or preassemble power
cable. Refer to your local electrical code(s) when applying 16 AWG wire or cable
in a motor circuit.
ATTENTION: Select the motor branch circuit protection that complies with the
NFPA79/ or NFPA70 (NEC) and any other governing regional or local codes.
WARNING: Do not install the ArmorStart LT where the maximum available
fault current exceeds the product rating.