beautypg.com

Quick reference troubleshooting – Rockwell Automation 294E ArmorStart LT EtherNet/IP Version - User Manual User Manual

Page 160

background image

160

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Chapter 5

Diagnostics

Quick Reference
Troubleshooting

The LEDs on the front of the ArmorStart LT provide an indication as to the
health of the device and network. The following is a brief troubleshooting guide.

Table 26 - LED Status Indication

Status LED

Description

Recommended Action

PWR (Control) Status Indicator

Off

The PWR LED is not illuminated at all.

Verify power is connected and with proper polarity.

Green

Voltage is present.

No action

Flashing Yellow

Power has fallen below minimum acceptable level.

Verify that the control power is between 19.2 and 26V DC.

RUN/FLT Status Indicator

Off

The RUN/FLT LED is not illuminated when a Run command has
been issued.

Verify that PLC is in Run mode. Verify that the correct run
bit is being controlled. Verify that a stop condition does
not exist.

Green

Valid start command

No action

Flashing Red

Protection fault

Count flashes and refer to Table 27 and 28.

MS – Module Status Indicator

Off

The MS LED is not illuminated.

Check to make sure the product is properly wired and
configured on the network.

Steady Green

Device configured and operational

No action

Flashing Green

Device IP Address has not been configured. .

Configure IP Address

Flashing Red

Resettable protection fault exists.

Verify fault by reviewing [TripStatus] Parameter 16 and
[TripLog0…4] Parameters 18…22. Correct and press the
blue reset button.

Solid Red

Non-resettable protection fault exists.

Verify fault by reviewing [TripStatus] Parameter 16 and
[TripLog0…4] Parameters 18…22. Correct and cycle
control power (switched and unswitched).

Flashes Green-Red

Self-test on power up

No action

NS – Network Status Indicator

Off

The NS LED is not illuminated.

Check to make sure the product is properly wired
and configured on the network.

Steady Green

CIP connection is established.

No action

Flashing Green

An IP address is configured, but no CIP connections are
established, and an Exclusive Owner connection has not timed
out.

Check to make sure the product is properly wired
and configured on the network.

Flashing Red

Connection has timed out.

Check to make sure the PLC is operating correctly and that
there are no media/cabling issues. Check to see if other
network devices are in a similar state.

Solid Red

Duplicate IP address detected

Check for node address conflict and resolve.

Flashes
Green-Red

The device has not completed the initialization, is not on an
active network, or has not finished self test at power up.

Remove or change the IP address of the conflicting device.

LS1 and LS2 Port Activity/Status

Off

No link established.

Verify network connection.

Green

Link established at 100 Mbps.

No action

Flashing Green

Transmit or receive activity present at 100 Mbps.

No action

Yellow

Link established at 10 Mbps.

No action