beautypg.com

Tcp/ip interface object, Class code 0x00f5 – Rockwell Automation 294E ArmorStart LT EtherNet/IP Version - User Manual User Manual

Page 223

background image

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

223

CIP Information

Appendix B

TCP/IP Interface Object

CLASS CODE 0x00F5

The following class attributes will be supported.

One Instance of the TCP/IP Interface Object will be supported.

4

Warning 4

5

Warning 5

Indicates missing supply phase. This fault can be disabled.

6

Jam Warning

Motor current has exceeded jam warning level.

7

Underload Warning

Motor current dropped below Underload Warning level.

8

Warning 8

9

Warning 9

10

Warning 10

11

Warning 11

12

Warning 12

13

Switched Pwr Warn

Indicates the control power has dipped below 19 Volts.

Not available in units with Integrated Power Supply.

14

Under Power Warn

Indicates the internal power supply is below its optimal level.

Available in units with Integrated Power Supply only.

15

Warning 15

16

Warning 16

17

Warning 17

18

Warning 18

19

Warning 19

20

Warning 20

21

Aux Power Warn

Indicates auxiliary Power was has dipped below 19 Volts.

Not available in units with Integrated Power Supply.

Table 35 - Fault Codes, Fault Text, and Fault Help Strings for ArmorStart LT

Warning

Code

Warning Text

Help Text

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Revision

UINT

2

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Status

DWORD

2

Get

Configuration Capability

DWORD

0x000000F4

3

Get/Set

Configuration Control

DWORD

0 = Configuration from NVS
2 = Configuration from DHCP

4

Get

Physical Link Object

Struct of:

UINT
Padded EPATH

2 words
20 F6 24 01 (Enet Link Object Instance 1)