Starter protection group – Rockwell Automation 294E ArmorStart LT EtherNet/IP Version - User Manual User Manual
Page 138
138
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 4
Bulletin 290E/291E/294E Programmable Parameters
Starter Protection Group
The functions highlighted are enabled by default
ProtFltResetMode
This parameter configures the Protection
Fault reset mode.
0 = Manual
1 = Automatic
Parameter Number
41
Access Rule
GET/SET
Data Type
BOOL
Group
Starter Protection
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
ProtectFltEnable
This parameter enables the Protection
Fault by setting the bit to 1.
Parameter Number
42
Access Rule
GET/SET
Data Type
WORD
Group
Starter Protection
Units
—
Minimum Value
0
Maximum Value
0xFFFF
Default Value
0xBFFF
Bit
Function
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
— — — — — — — — — — — — — — —
X
OverloadTrip
— — — — — — — — — — — — — —
X
—
PhaseShortTrip
— — — — — — — — — — — — —
X
— —
UnderPowerTrip
— — — — — — — — — — — —
X
— — —
SensorShortTrip
— — — — — — — — — — —
X
— — — —
OverCurrentTrip
— — — — — — — — — —
X
— — — — —
NonVolMemoryTrip
— — — — — — — — —
X
— — — — — —
ParamSyncTrip
— — — — — — — —
X
— — — — — — —
DCBusTrip/
OpenDisconnect
— — — — — — —
X
— — — — — — — —
StallTrip
— — — — — —
X
— — — — — — — — —
OverTemperature
— — — — —
X
— — — — — — — — — —
GroundFault
— — — —
X
— — — — — — — — — — —
RestartRetries
— — —
X
— — — — — — — — — — — —
DriveHdwFault
— —
X
— — — — — — — — — — — — —
OutputShortTrip
—
X
— — — — — — — — — — — — — —
UserDefinedTrip
X
— — — — — — — — — — — — — — —
HardwareFltTrip