Bulletin 290E/291E/294E Programmable Parameters

AccelTime1

Sets the rate of acceleration for all speed increases.

Parameter Number

36

Related Parameters

33, 37

Access Rule

GET/SET

Data Type

UINT

Group

Speed Control

Units

x.x secs

Minimum Value

0.0

Maximum Value

600.0

Default Value

10.0

DecelTime1

Sets the rate of deceleration for all speed decreases.

Parameter Number

37

Related Parameters

33, 36

Access Rule

GET/SET

Data Type

UINT

Group

Speed Control

Units

x.x secs

Minimum Value

0.1

Maximum Value

600.0

Default Value

10.0

Maximum Freq

Accel Time

--------------------------------------

Accel Rate

=

Parameter 35

(Maximum Freq)

Speed

Accel

Time 1

0

0

Time

Decel

Time 1

Acc

eler

ation

Dec

eler

ation

Maximum Freq

Decel Time

--------------------------------------

Decel Rate

=

Parameter 35

(Maximum Freq)

Speed

Accel

Time 1

0

0

Time

Decel

Time 1

Acc

eler

ation

Dec

eler

ation

SCurvePercent

Sets the percentage of acceleration or
deceleration time that is applied to ramp
as S Curve. Time is added, half at the
beginning and half at the end of the ramp.

Parameter Number

38

Access Rule

GET/SET

Data Type

UINT

Group

Speed Control

Units

Percentage

Minimum Value

0

Maximum Value

100

Default Value

0