Rockwell Automation 294E ArmorStart LT EtherNet/IP Version - User Manual User Manual
Page 77

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
77
Product Commissioning
Chapter 3
Figure 52 - E-mail Notification Configuration
E-mail triggers:
•
when a trip occurs
•
when a trip is cleared
•
when a warning occurs
•
when a warning is cleared
The following is an example trip e-mail:
Subject:
ArmorStart LT 291E 1.1-7.6A has detected an Overload Trip
Body:
Trip Snapshot:
SnapShotL1Amps: 1.11 Amps
SnapShotL2Amps: 2.22 Amps
SnapShotL3Amps: 3.33 Amps
SnapShotAveAmps: 2.22 Amps
SnapShot%Thermal: 55%
Trip Type:
Overload Trip
Trip Info:
Load has drawn excessive current based on the trip
class selected.
Device Name:
ArmorStart LT 291E Test Unit
Device Description:Latest AB On-Machine Offering
Device Location:
Sixth Floor Comms Lab
Contact Info:
Contact 1 Info: Slicia Turnbull in California
Contact 2 Info: Steve Plummer on Friday
IMPORTANT
“Cleared Event” e-mails will only be sent when all events have been cleared
and if a trip event e-mail has previously been sent.