Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
201
CIP Information
Appendix B
Instance 150
Instance 150 is the default Output (Consumed) Assembly for Bulletin 290E/
291E starters.
Instance 152
Instance 152 is the Exhaustive Starter Status Assembly for Bulletin 290E/291E
starters.
Instance 150 "Starter Cmd" – DeviceLogix Consumed Assembly for Bulletin 290E/291E Starters
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0 —
—
—
—
—
ResetFault
RunReverse
RunForward
1
—
—
Out05
Out04
Out03
Out02
Out01
Out00
2 Pt07DeviceIn
Pt06DeviceIn
Pt05DeviceIn
Pt04DeviceIn
Pt03DeviceIn
Pt02DeviceIn
Pt01DeviceIn
Pt00DeviceIn
3 Pt15DeviceIn
Pt14DeviceIn
Pt13DeviceIn
Pt12DeviceIn
Pt11DeviceIn
Pt10DeviceIn
Pt09DeviceIn
Pt08DeviceIn
4
AnalogDeviceIn (low byte)
5
AnalogDeviceIn (high Byte)
Instance 152 "Starter Stat" – DeviceLogix Produced Assembly for Bulletin 290E/291E Starters
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0 Reserved
1 Reserved
2
Reserved
3
Reserved
4
CurrentFlowing
NetControlStatus
Ready
RunningReverse
RunningForward
WarningPresent
TripPresent
5
DisconnectClosed
KeyPadHand
KeyPadOff
KeyPadAuto
DLXEnabled
6
Pt05
Pt04
Pt03
Pt02
Pt01
Pt00
7
8
Pt07DeviceOut
Pt06DeviceOut
Pt05DeviceOut
Pt04DeviceOut
Pt03DeviceOut
Pt02DeviceOut
Pt01DeviceOut
Pt00DeviceOut
9
Pt15DeviceOut
Pt14DeviceOut
Pt13DeviceOut
Pt12DeviceOut
Pt11DeviceOut
Pt10DeviceOut
Pt09DeviceOut
Pt08DeviceOut
10
An00DeviceOut (low byte)
11
An00DeviceOut (high byte)
12
Parameter 1 – PhaseL1Current
13
14
Parameter 2 – PhaseL2Current
15
16
Parameter 3 – PhaseL3Current
17
18
Parameter 4 – AverageCurrent
19
20
Parameter 5 – %ThermalUtilized
21