beautypg.com

Motor and control group – Rockwell Automation 294E ArmorStart LT EtherNet/IP Version - User Manual User Manual

Page 133

background image

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

133

Bulletin 290E/291E/294E Programmable Parameters Chapter 4

Motor and Control Group

SnapShotBusVolts

This parameter provides a snapshot of DC
bus voltage level at time of last trip.

Parameter Number

26

Access Rule

GET

Data Type

UINT

Group

Trip Status

Units

V DC

Minimum Value

0

Maximum Value

1200

Default Value

0

SnapShotDrvTemp

This parameter provides a snapshot of
operating temperature at time of last trip.

Parameter Number

27

Access Rule

GET

Data Type

UINT

Group

Trip Status

Units

°C

Minimum Value

0

Maximum Value

9999

Default Value

0

MotorNPVolts

Set to the motor nameplate rated voltage.

Parameter Number

28

Access Rule

GET/SET

Data Type

UINT

Group

Motor and Control

Units

V AC

Minimum Value

35

Maximum Value

460

Default Value

460

MotorNPHertz

Set to the motor nameplate rated
frequency.

Parameter Number

29

Access Rule

GET/SET

Data Type

UINT

Group

Motor and Control

Units

Hz

Minimum Value

10

Maximum Value

400

Default Value

60

O

Stop drive before changing this
parameter.

Stop drive before changing this
parameter.

O