C15340 | sdi: normal operation monitoring, C15341 | sdi: delay time, C15342 | sdi: tolerance threshold – Lenze E94AYAE SM301 User Manual
Page 91: C15343 | sdi: error response, C15340, C15341, C15342, C15343, 5parameter reference

Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05
91
5
Parameter reference
5.1
Parameter list | C15340
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C15340
C15341
C15342
C15343
Parameter | Name:
C15340 | SDI: Normal operation monitoring
Data type: UNSIGNED_8
Index: 9235
d
= 2413
h
From V1.3
Setting of the direction monitoring of the motor during normal operation.
Selection list
(Lenze setting printed in bold)
0 Both directions enabled
1 Positive direction enabled
2 Negative direction enabled
Read access Write access CINH PLC-STOP No transfer Scaling factor: 1
Parameter | Name:
C15341 | SDI: Delay time
Data type: UNSIGNED_16
Index: 9234
d
= 2412
h
From V1.3
Safely monitored time from activation up to switching on of the SDIpos/SDIneg monitoring.
Setting range
(min. value | unit | max. value)
Lenze setting
0
ms
30000 0 ms
Read access Write access CINH PLC-STOP No transfer Scaling factor: 1
Parameter | Name:
C15342 | SDI: Tolerance threshold
Data type: UNSIGNED_32
Index: 9233
d
= 2411
h
From V1.3
Setting of the tolerance threshold by how many increments the motor may move in the direction locked by SDI.
Setting range
(min. value | unit | max. value)
Lenze setting
0
Incr.
327680 0 incr.
Read access Write access CINH PLC-STOP No transfer Scaling factor: 1
Parameter | Name:
C15343 | SDI: Error response
Data type: UNSIGNED_8
Index: 9232
d
= 2410
h
From V1.3
Response to a violation of the permissible direction of movement of the motor.
Selection list
(Lenze setting printed in bold)
Info
0 STO
1 SS1
2 SS2
Read access Write access CINH PLC-STOP No transfer Scaling factor: 1