3safe configuration – Lenze E94AYAE SM301 User Manual

Page 32

background image

3

Safe configuration

3.6

General parameters

32

Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

The following speed-dependent functions require information from the safe speed measurement:

Ramp monitoring (SS1/SS2)

( 48)

Safe stop 2 (SS2)

( 46)

• Safe operating stop (SOS)

up to SM301 V1.2

in accordance with EN 61800-5-2 / SOS is speed-monitored

Safe maximum speed (SMS)

( 51)

Safely limited speed (SLS)

( 52)

• Safe speed monitor (SSM)

The following position-dependent functions require information from the safe position detection:

• Safe operating stop (SOS)

• in accordance with EN 61800-5-2 standard / SOS is position-monitored

(from SM301 V1.3)

Safe direction (SDI)

( 58)

• Safely limited increment (SLI)

Note!

The speed-dependent functions must not be parameterised if "No encoder system" is

set. The plausibility check rejects such implausible settings until they have been

parameterised correctly.

Stop!

Malfunctions due to slip, shaft fractures, etc.
Due to slip, shaft fractures, etc. between the motor and the encoder system, the safe

speed measurement is faulty.
Possible consequences:

• The speed-dependent functions are executed incorrectly.

Protective measures:

• Prevent malfunctions by constructive measures.
• Use motors and encoder systems with guaranteed qualities. Your Lenze contact

person will inform you about suitable systems.

• This must also be observed in the event of service for the motor or encoder system.