Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05

55

3

Safe configuration

3.9

Safety functions

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Function

 Basic status of normal operation
 If special operation is requested, the stop function (

STO

,

SS1

or

SS2

) parameterised for

special operation is started.

 Via enable through the enable switch, the motion function (

SLS

or free traversing)

parameterised for special operation is possible. Furthermore the SLI monitoring function

(safely limited increment) can be switched on for the motion function parameterised.

Parameter

C15200

OMS: Stop function

C15201

OMS: Motion function

• The "Free traversing" setting must be suitable for the application!

C15202

OMS: Function at LOW level

C15203

Safely limited increment

Requesting the

special operation

How to request the special operation:

• "ON state" at a safe input to which the "operation mode selector" function has been assigned

by parameter setting.

Safe inputs ( 34)

• Only if no safe input is used, the function can be activated via the safety bus by sending a data

telegram with a corresponding content to the controller.

If the OMS bit is received via the safety bus, the value 0 (normal operation) is adopted in the case

of passivation. In special applications (e.g. safety door requests OMS, i.e. open safety door =

special operation), this must not lead to a dangerous state through an automatic restart!

Deactivating

special operation

A change-over from special operation to normal operation is only possible when the drive is at

standstill (stop function

STO

,

SS1

or

SS2

active).

• For a restart, the restart must be acknowledged (AIS) via terminal or safety bus.

• The automatic restart is not permitted. If the "Automatic restart" is parameterised, this must

be prevented by special measures, e.g. programming in the master control.

Error behaviour

• The monitoring functions

SMS

and

SLS

can be activated in both operating modes and trigger

the parameterised stop function in the event of a error.

• If the SLI monitoring function is active, exceeding the position window activates the

parameterised stop function for special operation.

• The emergency stop function can be triggered in both operating modes.

Operation Mode Selector / OMS

Standard operation

Acknowledge (AIS)

for restart

Special operation

Stop function

Enable switch (ES)

Motion function

Activate OMS

Deactivate OMS

Œ

0

1

2

Ž