1 safe maximum speed (sms), Safe maximum speed (sms), 3safe configuration – Lenze E94AYAE SM301 User Manual
Page 51
![background image](/manuals/565743/51/background.png)
Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05
51
3
Safe configuration
3.9
Safety functions
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
3.9.2.1
Safe maximum speed (SMS)
Safe Maximum Speed / SMS
Description
The safety module monitors the adjusted safe maximum speed of the motor.
The function can only be activated by parameter setting.
• See parameter "SMS: Maximum speed Nmax".
• The function must not be parameterised if "No encoder system" is set. The plausibility check
rejects such implausible settings until they have been parameterised correctly.
Function
Parameter
SMS: Max. speed Nmax
• A value > 0 activates the function, a value = 0 deactivates the function.
SMS: Reaction (n>Nmax)
• Selection of the function to be executed (
) if monitoring
responds.
SLS, SMS: Max. response time
• If in the event of an error the speed is still outside the limit values after
the response time has elapsed,
is tripped immediately.
• Detailed information can be found in the chapter "
Activate
How to activate the function:
• Set the parameter "SMS: Maximum speed Nmax" > 0.
Error behaviour
If the speed exceeds the set maximum speed Nmax, an error message is generated and an error
stop is started with the function set in the parameter "SMS: Reaction (n>Nmax)" (
or
).
Nmax
t
0
SLS1
n
SMS
-Nmax
STO/SS1/SS2