Safety address invalid (0 or 0xffff) [0x012f0021, Profisafe communication error [0x012f0022, F_wd_time exceeded [0x012f0023 – Lenze E94AYAE SM301 User Manual

Page 109: Profisafe passivated [0x012f0024, 0x012f0023, 0x012f0022, 0x012f0024, 0x012f0021, 6error messages

background image

Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05

109

6

Error messages

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Safety address invalid (0 or 0xFFFF) [0x012f0021]

PROFIsafe communication error [0x012f0022]

F_WD_Time exceeded [0x012f0023]

PROFIsafe passivated [0x012f0024]

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

33

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Invalid effective safety address.

• Only for SM300

• Check safety address in the configuration software of

the control system.

• Check DIP switches on the SM300 safety module.

• Check safety address in the safe parameterisation.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

34

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

PROFIsafe data processing has detected a

communication error.

Check cabling between the communication module and

the control system.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

35

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

PROFIsafe monitoring time exceeded.

• Check program runtime of safety program.

• Increase monitoring time F_WD_Time.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

36

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

A fault has occurred in the PROFIsafe data processing.

PROFIsafe node is passivated.

• Check communication module, bus connection and

control program.

• Read out fault memory of control system.