No safe parameter set safety module [0x012f00a4, Defective parameter set safety module [0x012f00a5, Parameter set plausibility error [0x012f00a7 – Lenze E94AYAE SM301 User Manual

Page 123: 0x012f00a6, 0x012f00a4, 0x012f00a7, 0x012f00a5, 6error messages

background image

Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05

123

6

Error messages

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

No safe parameter set safety module [0x012f00a4]

Defective parameter set safety module [0x012f00a5]

Memory module - parameter set format error [0x012f00a6]

Parameter set plausibility error [0x012f00a7]

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

164

Response (Lenze setting printed in bold)

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Safety module has no parameter set.

Transfer safe parameter set via Engineer into safety

module.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

165

Response (Lenze setting printed in bold)

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Parameter set on safety module is defective.

Transfer safe parameter set via Engineer into safety

module.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

166

Response (Lenze setting printed in bold)

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

A format error has been detected in the parameter set of

the memory module.

Recreate the parameter set format using the "General

reset" function and transfer the parameter set via the

Engineer into the safety module.

Module ID (decimal)

Error ID (decimal)

303: SM301 safety module

167

Response (Lenze setting printed in bold)

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The set parameters are not plausible with regard to each

other.

Select the parameter set in the Engineer. Call the

plausibility check and transfer the parameter set via the

Engineer into the safety module.