C15204 | sli: value of position change, C15205 | sse: emergency stop function, C15300 | restart behaviour – Lenze E94AYAE SM301 User Manual
Page 86: C15305 | ss1, ss2: stopping time, C15205, C15300/1, C15300/2, C15305, 5parameter reference

5
Parameter reference
5.1
Parameter list | C15204
86
Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C15204
C15205
C15300
C15305
Parameter | Name:
C15204 | SLI: Value of position change
Data type: UNSIGNED_32
Index: 9371
d
= 249B
h
From V1.4
Value of the maximum position change while SLI has been active.
Display range
(min. value | unit | max. value)
0
Incr.
2147483647
Read access Write access CINH PLC-STOP No transfer Scaling factor: 1
Parameter | Name:
C15205 | SSE: Emergency stop function
Data type: UNSIGNED_8
Index: 9370
d
= 249A
h
Selection of the stop function for emergency stop.
Selection list
(Lenze setting printed in bold)
Info
0 STO
1 SS1
Read access Write access CINH PLC-STOP No transfer Scaling factor: 1
Parameter | Name:
C15300 | Restart behaviour
Data type: UNSIGNED_8
Index: 9275
d
= 243B
h
Setting of the restart behaviour after deactivation of the STO, SS1, SS2 and SOS standstill function.
Selection list
0 Acknowledged restart
1 Automatic restart
Subcodes
Lenze setting
Info
C15300/1
0: Acknowledged restart
Restart - STO, SS1
C15300/2
0: Acknowledged restart
Restart - SS2, SOS
Read access Write access CINH PLC-STOP No transfer Scaling factor: 1
Parameter | Name:
C15305 | SS1, SS2: Stopping time
Data type: UNSIGNED_16
Index: 9270
d
= 2436
h
Stopping time for the SS1 and SS2 safety functions.
Setting range
(min. value | unit | max. value)
Lenze setting
0
ms
30000 0 ms
Read access Write access CINH PLC-STOP No transfer Scaling factor: 1