C15003 | command status, C15010 | parameter set status, C15011 | parameter crc – Lenze E94AYAE SM301 User Manual
Page 73: 5parameter reference
Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05
73
5
Parameter reference
5.1
Parameter list | C15003
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C15003
C15010
C15011
Parameter | Name:
C15003 | Command status
Data type: UNSIGNED_16
Index: 9572
d
= 2564
h
Status of the current command.
• The command is repeated in the high byte.
• In the low byte the status is displayed:
0x00: No command
0x01: Command executed
0x02: Password invalid
0x03: Command in process
0x04: Command not known
0x05: Command error
Display range
(min. value | unit | max. value)
0
2309
Read access Write access CINH PLC-STOP No transfer Scaling factor: 1
Parameter | Name:
C15010 | Parameter set status
Data type: UNSIGNED_8
Index: 9565
d
= 255D
h
Status of the parameter set.
Selection list
(read only)
0 No parameter set
1 Parameter set valid
2 Read error - memory module
3 Unequal parameter set
4 CRC error
5 Version error
6 Format error
7 Plausibility error
8 Assignment error
9 Local read error
10 GG communication error
Read access Write access CINH PLC-STOP No transfer Scaling factor: 1
Parameter | Name:
C15011 | Parameter CRC
Data type: UNSIGNED_32
Index: 9564
d
= 255C
h
Parameter checksum (CRC = Cyclic Redundancy Code).
Display range
(min. value | unit | max. value)
0
4294967295
Subcodes
Info
C15011/1
CRC safety module
C15011/2
CRC memory module
Read access Write access CINH PLC-STOP No transfer Scaling factor: 1