C15200 | oms: stop function, C15201 | oms: motion function, C15202 | oms: function at low level – Lenze E94AYAE SM301 User Manual
Page 85: C15203 | sli: safely limited increment, Meterised via, C15202, C15200, C15201, C15203, C15035

Lenze · SM301 safety module · Parameter setting & configuration · DMS 2.3 EN · 11/2013 · TD05
85
5
Parameter reference
5.1
Parameter list | C15200
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C15200
C15201
C15202
C15203
Parameter | Name:
C15200 | OMS: Stop function
Data type: UNSIGNED_8
Index: 9375
d
= 249F
h
Selection of the stop function during special operation.
Selection list
(Lenze setting printed in bold)
Info
0 STO
1 SS1
2 SS2
Read access Write access CINH PLC-STOP No transfer Scaling factor: 1
Parameter | Name:
C15201 | OMS: Motion function
Data type: UNSIGNED_8
Index: 9374
d
= 249E
h
Selection of the motion function during special operation.
Selection list
(Lenze setting printed in bold)
Info
3 SLS1
4 SLS2
(from V1.1)
5 SLS3
(from V1.1)
6 SLS4
(from V1.1)
11 Free traversing
Read access Write access CINH PLC-STOP No transfer Scaling factor: 1
Parameter | Name:
C15202 | OMS: Function at LOW level
Data type: UNSIGNED_8
Index: 9373
d
= 249D
h
From V1.3
Danger!
If the operation mode selector is implemented via a safe input, the operating mode for the LOW level must be
selected carefully. According to the closed-circuit principle, there must not arise any additional danger from normal
or special operation in the corresponding application.
For detailed information, please see the manual for the safety module.
Selection list
(Lenze setting printed in bold)
Info
0 Normal operation
1 Special operation
Read access Write access CINH PLC-STOP No transfer Scaling factor: 1
Parameter | Name:
C15203 | SLI: Safely limited increment
Data type: UNSIGNED_32
Index: 9372
d
= 249C
h
From V1.4
Number of increments for safely limited increment.
• Value "0" deactivates the SLI function.
Setting range
(min. value | unit | max. value)
Lenze setting
0
Incr.
2147483647 1 inc.
Read access Write access CINH PLC-STOP No transfer Scaling factor: 1