Setting of the operation mode, Bulletin f-107-uxf3 – Dwyer UXF3 User Manual

Page 76

background image

-68-

4.10.8. Setting of the operation mode

Description
z Used to switch computation cycle and output cycle.
z Settable range

NORMAL

: Standard mode (factory-set value), computation/output cycle is approximately 0.5 seconds.

HIGH SPEED : High speed response mode, computation/output cycle is approximately 0.2 seconds.

For actual keying, refer to the typical operation indicated below. Set the parameter protection to OFF beforehand. (See Section 4.4.1.)

Operation
(example)

Switch the operation mode to the high speed response mode.

Key operation

Description

Display

ź

Press the

key twice to display “OUTPUT SETTING”.

OUTPUT SETTING

ENT

ź

Press the

ENT

key once to display “ZERO ADJUSTMENT”.

ZERO ADJUSTMENT

SET ZERO

ź

Press the

key 12 times to display “OPERATION MODE”.

OPERATION MODE

NORMAL

ENT

ź

Press the

ENT

key once to blink the cursor.

OPERATION MODE

NORMAL

ź

Press the

key 6 times to move the cursor.

OPERATION MODE

HIGH SPEED

Press the

ENT

key once to register.

OPERATION MODE

COMPLETE

Ļ

ENT

ź
ź
ź
ź

ʊʊʊ “OPERATION MODE” has been registered. ʊʊʊ

OPERATION MODE

HIGH SPEED

ESC

Press the

ESC

key once and then press the

key 3 times to enter

the measurement mode.

0.000 %
0.000 m3/h

Reference

The difference between standard mode and high speed mode:
High speed mode is unfit for the measurement when foreign objects or air bubbles are contained.
Standard mode is about 10 times more resistant to entry of foreign objects or air bubbles than high speed mode.

Bulletin F-107-UXF3