4.10.5.2. How to validate the alarm output

Description
z Select a contact output as DO1 and/or DO2 when received wave or E

2

PROM is abnormal.

z Settable range

ALL

: Select a contact output when hardware and received wave (nothing, unstable) are abnormal.

HARDWARE FAULT : Select a contact output when circuit is abnormal.
PROCESS ERROR : Select a contact output when received wave is abnormal.

For actual keying, refer to the typical operation indicated below. Set the parameter protection to OFF beforehand. (See Section 4.4.1.)

Operation
(example)

Set the DO1 output to “PROCESS ERROR”.
Also, set the contact to “ACTIVE ON”.

Key operation

Description

Display

ź

Press the

key twice to display “OUTPUT SETTING”.

OUTPUT SETTING

ENT

ź

Press the

ENT

key once to display “ZERO ADJUSTMENT”.

ZERO ADJUSTMENT

SET ZERO

ź

Press the

key 6 times to display “DO1 OUT”.

* Press the

key again to display “DO2 OUT”.

* Press the

key once again to display “DO3 OUT”.

DO1 OUT

NOT USED

ENT

ź

Press the

ENT

key once to blink the cursor.

DO1 OUT

NOT USED

ź

Press the

key 4 times to display “ALARM” on the 2nd line.

DO1 OUT

ALARM

ENT

ź

Press the

ENT

key once to display the ALARM select panel.

ALARM

ALL

ź

Press the

key twice to display “PROCESS ERROR”.

ALARM

PROCESS ERROR

Press the

ENT

key once to register.

ALARM

COMPLETE

Ļ

ENT

ź
ź
ź
ź

ʊʊʊ “PROCESS ERROR” has been registered. ʊʊʊ

STATUS OUT

CONTACT ACTION

ENT

ź

Press the

ENT

key once to display “CONTACT ACTION”.

CONTACT ACTION

ACTIVE ON

Press the

ENT

key once to register “ACTIVE ON”(normally off).

* To select normally on, press the

key.

CONTACT ACTION

COMPLETE

Ļ

ENT

ź
ź
ź
ź

ʊʊʊ “ACTIVE ON” has been registered. ʊʊʊ

STATUS OUT

CONTACT ACTION

ESC

Press the

ESC

key twice and then press the

key 3 times to enter

the measurement mode.

0.000 m/s
0.000 m3/h