Selecting a reference pulse form – Yaskawa FSP Amplifier User Manual
Page 83

FSP Amplifier User’s Manual
Chapter 5: Parameter Settings and Functions
5-16
This circuit uses the 12 V power supply built into the servo amplifier. The
input is not isolated in this case.
Ω
Ω
FSP Amplifier
Note: The noise margin of the input signal will decrease if the reference pulse is provided by an open-collector
output. Set parameter Pn200.3 to 1 if the position drifts due to noise.
Selecting a Reference Pulse Form
Use the following parameters to select the reference pulse form used.
Ö
Input PULS CN1-7
Reference Pulse Input
Position Control
Ö
Input /PULS CN1-8
Reference Pulse Input
Position Control
Ö
Input SIGN CN1-11
Reference Code Input
Position Control
Ö
Input /SIGN CN1-12
Reference Code Input
Position Control
The servomotor only rotates at an angle proportional to the input pulse.
Parameter Signal
Setting
Control
Mode
Pn200.0
Reference Pulse Form
Default Setting: 4
Position Control and
Programming
Set reference pulse form input to the servo amplifier from the host
controller.
Note: This function works only with a Pulse Reference, not with a Serial Command.
CN1-7
CN1-11
PULSE
SIGN
Position
reference
pulse
FSP Amplifier
Host
controller
Since the reference pulse form can be selected from among those listed on
the next page, set one according to host controller specifications.