FSP Amplifier User’s Manual

Chapter 5: Parameter Settings and Functions

5-71


To use the /NEAR signal, an output terminal must be allocated with the
parameter below.

Parameter Signal

Setting

Control

Mode

Pn510

Output Signal

Selections 3

Default Setting: 0000

Position Control

5.5.8. Handling Power Loss

The following parameter is used to specify whether to generate an alarm
when power loss occurs.

Parameter Signal

Setting

(ms)

Control Mode

Pn509

Momentary Hold Time

Range: 20 to 1000
Default Setting: 20

Speed, Torque,
Position Control, and
Programming

The servo amplifier turns the servomotor OFF if it detects a voltage drop in
the power supply. The default setting of 20 ms means that servomotor
operation will continue if power is lost for less than 20 ms.
In the following instances, however, either a servo alarm is generated or
control is lost (equivalent to normal power OFF operation) regardless of
the parameter setting.
• When an insufficient voltage alarm (A.41) occurs during power loss

with a large servomotor load.

• Loss of the control power supply is equivalent to normal power OFF

operation, thus control is lost.

In power loss detection, the status of the main circuit power supply is
detected and OFF status is ignored so that the servomotor’s operation will
continue if motor power turns back ON within the time set at user constant
Pn509.

Time

Power supply
voltage

t OFF

Power loss

1

.

Pn509

setting t > t OFF

2

.

Pn509

setting t < t OFF

For

1.

For

2.

Servo ON

Servo ON

Servo OFF

5