A.d0: position error pulse overflow, Display and outputs, Status and remedy for alarm – Yaskawa FSP Amplifier User Manual
Page 299

FSP Amplifier User’s Manual
Chapter 9: Inspection, Maintenance, and Troubleshooting
9-34
A.d0: Position Error Pulse Overflow
Display and Outputs
Alarm Outputs
Alarm Code Output
ALO1 ALO2
ALO3
ALM Output
ON ON
OFF
OFF
Note: OFF: Output transistor is OFF (alarm state).
ON: Output transistor is ON.
Status and Remedy for Alarm
During servomotor operation.
At power ON.
A
E
During high speed
rotation.
When a long reference is
entered during normal
operation.
When a properly entered
reference pulse does not
generate a feedback
pulse.
A
B, C, D
E
Cause of the Problem
Solution
A
Servomotor wiring incorrect or
poor connection
Check wiring and connectors at encoder.
B
Servo amplifier was not
correctly adjusted.
Increase speed loop gain (Pn100) and
position loop gain (Pn102).
C
Motor load was excessive.
Reduce load torque or inertia. If problem
persists, replace with a larger capacity
motor.
D
Position reference pulse
frequency was too high.
•
Increase or decrease reference pulse
frequency.
•
Add smoothing function.
•
Correct electronic gear ratio.
E
Circuit board (1PWB) defective.
Replace servo amplifier.