Initializing parameter settings, Important – Yaskawa FSP Amplifier User Manual
Page 221

FSP Amplifier User’s Manual
Chapter 7: Using the Panel Operator
7-30
7.2.9. Initializing Parameter Settings
This function is used to reset all parameters to the default settings (standard
factory settings).
IMPORTANT
• Initialize the parameter settings with the servo OFF.
•
After performing the procedure, cycle the power to reset all the
parameters to the default settings.
Follow the procedure below to initialize parameter settings.
1.
Press the MODE/SET key to select the Auxiliary Function mode.
2.
Press the Up Arrow or Down Arrow key to select function Fn005.
3.
Press the DATA/SHIFT key for a minimum of one second, and the
display will be as shown below.
4.
Press the MODE/SET key, and the display will be as shown below.
The parameters will be initialized.
Flashing during
initialization
End
Flashing for
one second
5.
Press the DATA/SHIFT key for a minimum of one second to return to
the Auxiliary Function mode display.
This completes the initialization of parameter settings.
Note: Parameters will not be initialized by pressing the DSPL/SET or MODE/SET key with the servo ON. Turn
the power OFF and then back ON after initialization.