79
4.4.2
Rev B:
4.4.2.1
115VAC:
Test No.
Section
Subject
Test Limits
Comment
File Ref.
1.0
Normal AC Steady State
1.1
Individual Phase Voltage
100.0 to 122.0 Volts RMS
30 mins, 800Hz and 360Hz
LVAC-11
1.2
Average of Three-Phase Voltages
101.5 to 120.5 Volts RMS
30 mins, 800Hz and 360Hz
LVAC-12
1.3
Phase Displacement
120.0 +/- 4.0°
No specified test
1.4
Phase Voltage Unbalance
Max. 6.0 Volts RMS
Apply each test 30 mins
LVAC-14
1.5
AC Voltage Modulation
1.5.1
Maximum Amplitude
5.0 Volts Peak-to-Valley
Follows specification Figure 1
LVAC-15
1.5.2
Frequency Components
Per Figure 1
Figure only, not a test. (Refer to spec)
1.6
Voltage Waveform
1.6.1
Total Harmonic Content
Max. 10% of Fundamental
30 mins each test
LVAC-16-1
1.6.2
Individual Harmonic Content
Max. 8% of Fundamental
Requires audio generator
1.6.3
DC Content
+/-0.10 Volts (after first cycle)
30 mins each test
LVAC-16-3
1.6.4
Crest Factor
1.41 +/- 0.15
No specified test
1.7
Steady State Frequency (see Designer Notes)
360 to 800 Hz
Requirement fulfilled in 1.1 and 1.2
1.8
Frequency Modulation
Applies to Ground Handling Equip only
2.0
Normal AC Transients
2.1
Voltage Transients
50ms Dropouts
800Hz and 360Hz
LVAC-21-1
2.1
Voltage Transients
Voltage Surge/Sag
3 times each, 800Hz and 360Hz
LVAC-21-2
2.1
Voltage Transients
Per Table B.2.1.1.1
2 times each
LVAC-21-3
2.2
Voltage Spikes
Per Figure 10
Requires additional equipment
2.3.1
Frequency Variations - Max Ramp Rate
100Hz/s up, 200Hz/s down
3 times each, 360Hz nominal
LVAC-23
2.3.2
Frequency Variations - Frequency Transients
Applies to Ground Handling Equip only
3.0
Abnormal AC Steady State
3.1
Individual Phase Voltage
90.0 to 134.0 Volts RMS
Single Phase Unit Test
LVAC-31
3.2
Average of Three-Phase Voltages
91.5 to 132.5 Volts RMS
5 mins each test
LVAC-32-1
3.2
Average of Three-Phase Voltages
90.0 to 134.0 Volts RMS
Three Phase Unit Test
LVAC-32-2
3.3
Abnormal Steady State Frequency (see Designer Notes)
360 to 800 Hz
Requirement fulfilled in 1.7
4.0
Abnormal AC Transients
4.1
Voltage Transients
Per Figure 5A
Apply each transient 3x with 10s interval
LVAC-41