Avionics Software
5.3.6
Rev A:
5.3.6.1
Table SAC:
Test No. Section
Subject
Test Limits
Comment
File Ref.
SAC101
Load and Current Harmonic Measurements
115V RMS, 400 Hz
ASAC101
SAC102
Steady State Limits for Voltage and Frequency
108V to 118V RMS, 380 to 420 Hz
Apply for 30 mins each test
ASAC102
SAC103
No Test, Done so test numbers coincide
SAC104
Voltage Modulation
1
115V Nominal Test
115V RMS, 3.5V Vp-v mod
Apply for 10+ mins
ASAC104-1
2
109V Nominal Test
109V RMS, 3.5V Vp-v mod
Apply for 10+ mins
ASAC104-2
3
117V Nominal Test
117V RMS, 3.5V Vp-v mod
Apply for 10+ mins
ASAC104-3
SAC105
Frequency Modulation
1
400 Hz Nominal Test
400 Hz, +/-4 Hz mod
Apply for 10+ mins
ASAC105-1
2
395 Hz Nominal Test
395 Hz, +/-4 Hz mod
Apply for 10+ mins
ASAC105-2
3
405 Hz Nominal Test
405 Hz, +/-4 Hz mod
Apply for 10+ mins
ASAC105-3
SAC106
Voltage Distortion Spectrum
Requires Additional Equipment
SAC107
Total Voltage Distortion
Voltage Distortion Factor 0.08
Apply for 30 mins
ASAC107
SAC108
DC Voltage Component
1
Positive DC Offset
115V RMS + .10V DC
Apply for 30 mins
ASAC108-1
2
Negative DC Offset
115V RMS - .10V DC
Apply for 30 mins
ASAC108-2
SAC109
Normal Voltage Transients
160V RMS to 58V RMS
1
Overvoltage Transients
Peak voltage 160V RMS
Table SAC109-2 A-G
ASAC109-1
2
Undervoltage Transients
Low voltage 58V RMS
Table SAC109-2 H-N
ASAC109-2
3
Combined Transient
160V RMS to 58V RMS
Table SAC109-2 O
ASAC109-3
4
Repetitive Normal Voltage Transient Test
90V RMS to 140V RMS
Run transient for 30 mins
ASAC109-4
SAC110
Normal Frequency Transients
350 Hz to 450 Hz
1
Overfrequency Transients
High Frequency 425 Hz
Table SAC110-2 A-D
ASAC110-1
2
Underfrequency Transients
Low Frequency 350 Hz
Table SAC110-2 E-H
ASAC110-2
3
Combined Transient
350 Hz to 450 Hz
Table SAC110-2 I
ASAC110-3
SAC201
Power Interrupt
0V for 50 msec
Table SAC201-2 A-L
ASAC201
SAC301
Abnormal Steady State Limits for Voltage and Frequency
102V RMS to 124V RMS, 370 Hz to 430 Hz Apply for 30 mins
ASAC301
SAC302
Abnormal Voltage Transients
45V RMS to 180V RMS
1
Overvoltage Transients
Peak voltage 180V RMS
Table SAC302-2 A-G
ASAC302-1
2
Undervoltage Transients
Low voltage 45V RMS
Table SAC302-2 H-N
ASAC302-2
3
Combined Transient
45V RMS to 180V RMS
Table SAC302-2 O
ASAC302-3
SAC303
Abnormal Frequency Transients
320 Hz to 480 Hz
Table SAC303-2 A-E
ASAC303
SAC401
Emergency Steady State Limits for Voltage and Frequency
104V to 122V RMS, 360 Hz to 440 Hz
Apply for 30 mins
ASAC401
SAC501
No Tests
N/A to AC Utilization Equipment
SAC601
Power Failure (Single Phase)
0V for 7 seconds
Table SAC601-2 A-D
ASAC601
SAC602
Power Failure
No test, done so numbers coincide
SAC603
Phase Reversal
N/A to rev A