Programmer Operation

Installation and Operation Handbook

5-14

2408 and 2404 Controller

Ramp rate
Ramp rate for ‘

rmP.r’ segments

Using

or

, set a value for the ramp rate, ranging from 0.0 to

999.9. The units are the ramp units (

rmP.U) set earlier in this

sequence.

Press

Duration time
Time for a ‘

dwEl’ segment, or time to target for a ‘rmP.t’

segment.
Set the time using

or

. You have set the units earlier in

this sequence. [‘

dwL.U’ defines the units for ‘dwEl’ segments:

rmP.U’ defines the units for ‘rmP.t’ segments.]

Press

Called program number
Only appears for ‘

cALL’ segments.

(multi-program controllers only)

Set a called program number from 1 to 4, or from 1 to 20, using

or

.

Press

Number of cycles of the cALLed program
Only appears for ‘

cALL’ segments.

(multi-program controllers only)

Sets the number of cycles of the cALLed program from 1 to 999,
using

or

.

Press

Continued on the next page.