Thermcraft XST-6-0-36-3V User Manual
Page 240
Configuration
Installation and Operation Handbook
6-8
2416 Controller
Name
Description
Values
Meaning
iP
Input configuration
inPt
Input type
J.tc
J thermocouple
k.tc
K thermocouple
L.tc
L thermocouple
r.tc
R thermocouple (Pt/Pt13%Rh)
b.tc
B thermocouple (Pt30%Rh/Pt6%Rh)
n.tc
N thermocouple
t.tc
T thermocouple
S.tc
S thermocouple (Pt/Pt10%Rh)
PL 2
PL 2 thermocouple
C.tc
Custom downloaded t/c (default = type C)
rtd 100Ω platinum resistance thermometer
mV
Linear millivolt
voLt
Linear voltage
mA
Linear milliamps
Sr V
Square root volts
Sr A
Square root milliamps
* See ‘
CuSt’ List.
mV.C
8-point millivolt custom linearisation
*
V.C
8-point Voltage custom linearisation
*
mA.C
8-point milliamp custom linearisation
*
CJC
Cold Junction
OFF
No cold junction compensation
Compensation
Auto
Automatic internal compensation
0
o
C
0
o
C external reference
45
o
C
45
o
C external reference
50
o
C
50
o
C external reference
imp
Sensor Break Impedance
Off
Disabled (applies to any input)
Caution:
If sensor break is disabled the
controller will not detect open circuit
faults
Auto
Factory set
Hi
Impedance of input > 15K
Ω
Hi.Hi
Impedance of input > 30K
Ω
Linear Input Scaling
− The next four parameters only appear if a linear input is chosen.
inP.L
Input
value
low
inP.H
Input
value
high
VAL.L
Display reading low
VAL.H
Display reading high
VAL.L
inP.H
inP.L
VAL.H
Displayed Value
Electrical
Input