beautypg.com

Thermcraft XST-6-0-36-3V User Manual

Page 240

background image

Configuration

Installation and Operation Handbook

6-8

2416 Controller

Name

Description

Values

Meaning


iP

Input configuration

inPt

Input type

J.tc

J thermocouple

k.tc

K thermocouple

L.tc

L thermocouple

r.tc

R thermocouple (Pt/Pt13%Rh)

b.tc

B thermocouple (Pt30%Rh/Pt6%Rh)

n.tc

N thermocouple

t.tc

T thermocouple

S.tc

S thermocouple (Pt/Pt10%Rh)

PL 2

PL 2 thermocouple

C.tc

Custom downloaded t/c (default = type C)

rtd 100Ω platinum resistance thermometer

mV

Linear millivolt

voLt

Linear voltage

mA

Linear milliamps

Sr V

Square root volts

Sr A

Square root milliamps

* See ‘

CuSt’ List.

mV.C

8-point millivolt custom linearisation

*

V.C

8-point Voltage custom linearisation

*

mA.C

8-point milliamp custom linearisation

*

CJC

Cold Junction

OFF

No cold junction compensation

Compensation

Auto

Automatic internal compensation

0

o

C

0

o

C external reference

45

o

C

45

o

C external reference

50

o

C

50

o

C external reference

imp

Sensor Break Impedance

Off

Disabled (applies to any input)

Caution:

If sensor break is disabled the
controller will not detect open circuit
faults

Auto

Factory set

Hi

Impedance of input > 15K

Ω

Hi.Hi

Impedance of input > 30K

Ω

Linear Input Scaling

The next four parameters only appear if a linear input is chosen.

inP.L

Input

value

low

inP.H

Input

value

high

VAL.L

Display reading low

VAL.H

Display reading high

VAL.L

inP.H

inP.L

VAL.H

Displayed Value

Electrical
Input