Installation and Operation Handbook

Configuration

2416 Controller

6-7

Name

Description

Values

Meaning

pV

Process value config

unit

Instrument units

0

C

Celsius

0

F

Fahrenheit

0

k

Kelvin

none

Display units blanked

dec.p

Decimal places in the

nnnn

None

displayed

value

nnn.n

nn.nn

One

Two

rng.L

Range low

Low range limit. Also setpoint limit for
alarms and programmers

rng.h

Range high

High range limit. Also setpoint limit for
alarms and programmers

Notes:

1. Pyrometer Emmisivity

Controllers which are specifically supplied for pyrometer inputs (not Exergen K80), have the

curve downloaded in the Custom Input. The parameter,

EmiS, Pyrometer Emmisivity,

appears in the Input List on page 2-15. This parameter is also now correctly adjusted.

2. Range

If a decimal point was configured, negative display and setpoint ranges were limited to -99.9

in previous software versions. The range has been increased to -199.9 by combining the
negative sign with the figure one. This allows Setpoints, Process Variables, Alarm
Setpoints and Programmers to be set to -199.9.