Configuration
Installation and Operation Handbook
6-20
2408 and 2404 Controller
Name
Description
Values Meaning
4A
Module 4 configuration
Note: This option is not available on controllers from 01 Jan-04
id
Identity of module installed
HCS
High Current Switch
Func
Function
nonE Function disabled
dIG
Digital output function
HEAt Heating output
COOL Cooling output
VAL.L
% PID demand signal giving
minimum output
− ‘Out.L’
VAL.H
% PID demand signal giving
maximum output
− ‘Out.H’
Out.L
Minimum electrical output
Out.H
Maximum electrical output
SEnS
Sense of output
(Only if ‘
Func’ = ‘dIG’)
nor
Normal (output energises when
TRUE, e.g. program events)
inv
Inverted (output de-energises
when TRUE, e.g. alarms)
When ‘
SEnS’ appears, then further parameters are available.
These are identical to those in the ‘
AA ConF’ list on Page 6-14.
Cust
8-point Custom Linearisation
(1)
in 1
Custom input 1
VAL.1
Linearisation Value representing
in 1
in 8
Custom
input
8
VAL.8
Linearisation Value representing
in 8
VAL.L
Out.H
Out.L
VAL.H
PID Demand Signal
Electrical
Output
Note:
1. Custom Linearisation is only available when ‘
3a-Conf’ or iP- ConF list has
‘
inpt’ set to ‘mV.C’, or ‘mA.C’, or ‘V.C’.
2. The values and inputs must be continuously increasing or decreasing
VAL.1
VAL.3
in 8
in 1
in 3
VAL.8
Displayed Value
Electrical
Input