Thermcraft XST-6-0-36-3V User Manual
Page 276

Technical Specification
Installation and Operation Handbook
C-2
2416 Controller
Alarms
Number of alarms
Four
Alarm types
Absolute high or low. Deviation band, deviation high, deviation
low. Rate of change
Alarm modes
Latching or non-latching. Blocking. Energised or de-energised in
alarm
Setpoint programming
Number of programs
One or four
Segments per
program
16
Event outputs
Up to two
Communications (all modules are isolated)
Modbus
®
RS232,2-wire,RS 485 and 4 wire RS485 modules
Baud rate
1200, 2400, 4800, 9600 and 19,200 baud
PDSIO
Slave input (isolated)
Remote setpoint input with holdback to master
Master output
Isolated from main PV. Retransmission of setpoint, process value
or output
General
Display
Dual, 4 digit x 7 segment LED. Up to two decimal places
Supply
85 to 264Vac, 48 to 62 Hz, 10 W max OR
24Vdc or ac -15%, +20%. 10W max
Operating ambient
0 to 55
o
C and 5 to 90% RH non-condensing
Storage temperature
-10 to +70
o
C
Panel sealing
IP65
Dimensions
48mm wide x 48mm high x 150mm deep
Weight 250g
EMC standards
EN50081-2 & EN 50082-2 generic standards for industrial
environments
Safety standards
Meets EN61010, installation category II (voltage transients must not
exceed 2.5kV), pollution degree 2
Atmospheres
Not suitable for use above 2000m or in explosive or corrosive
atmospheres. Electrically conductive pollution must be excluded
from the cabinet in which this controller is mounted