User Calibration

Installation and Operation Handbook

7-4

2408 and 2404 Controller


Set Offset 1
Use

or

to set the offset value of Process Value 1

(PV1).
The offset value is in display units.

Press

Set Offset 2
Use

or

to set the offset value of Process Value 2

(PV2), if configured.
The offset value is in display units.

Press


The table below shows the parameters which appear after

OFS.2’. These are all read only values and are for information.

Press

to step through them.

mV.1

IP1 measured value (at terminals)

mV.2

IP2 measured value (at terminals), if DC input in
Module 3 position

CJC.1

IP1 Cold Junction Compensation

CJC.2

IP2 Cold Junction Compensation

Li.1

IP1 Linearised Value

Li.2

IP2 Linearised Value

PV.SL

Shows the currently selected input


If you do not want to look at these parameters, then press

and this returns you to the ‘

iP-LiSt’ header.

To protect the calibration against unauthorised adjustment, return
to Operator level and make sure that the calibration parameters
are hidden. Parameters are hidden using the ‘Edit’ facility
described in Chapter 3, Access Levels.

OFS.2

0

See table on

the right for

additional

parameters.

OFS.1

0