Ucal – Thermcraft XST-6-0-36-3V User Manual
Page 250
User Calibration
Installation and Operation Handbook
7-2
2416 Controller
7.2
USER CALIBRATION ENABLE
The User calibration facility must first be enabled in configuration level by setting the
parameter ‘
UCAL' in the CAL ConF list to 'YES'. This will make the User calibration
parameters visible in Operator ‘
FuLL’ level. This procedure is described in Chapter 6,
Configuration, but for convenience is summarised below: .
+
The Calibration Configuration List
Press
until you reach the ‘
CAL-Conf’ list.
Press
until you reach ‘
UCAL’.
User Calibration Enable
Use
or
to select:
•
YES:
Calibration enable
•
no:
Calibration disabled
Press
and
together to go to the
Exit display.
Exit configuration
Use
or
to select ‘
YES’ to return to Operator level.
CAL
UCAL
YES