User Calibration

Installation and Operation Handbook

7-2

2416 Controller

7.2

USER CALIBRATION ENABLE

The User calibration facility must first be enabled in configuration level by setting the
parameter ‘

UCAL' in the CAL ConF list to 'YES'. This will make the User calibration

parameters visible in Operator ‘

FuLL’ level. This procedure is described in Chapter 6,

Configuration, but for convenience is summarised below: .

+

The Calibration Configuration List

Press

until you reach the ‘

CAL-Conf’ list.

Press

until you reach

UCAL’.

User Calibration Enable

Use

or

to select:

YES:

Calibration enable

no:

Calibration disabled

Press

and

together to go to the

Exit display.

Exit configuration

Use

or

to select ‘

YES’ to return to Operator level.

CAL

UCAL

YES

Ч2