Conf, Inst – Thermcraft XST-6-0-36-3V User Manual
Page 234
Configuration
Installation and Operation Handbook
6-2
2416 Controller
6.1
SELECTING CONFIGURATION LEVEL
There are two alternative methods of selecting Configuration level:
• If you have already powered up, then follow the access instructions given in Chapter 3,
Access levels.
• Alternatively, press
and
together when powering up the controller. This will
take you directly to the ‘
ConF’ password display.
6.1.1 Password
entry
When the ‘
ConF’ display appears, you must enter the
Configuration password (which is a number) in order to
gain access to Configuration level.
Enter the password using the
or
buttons.
The configuration password is set to ‘
2’ when the
controller is shipped from the factory.
Once the correct password has been entered, there is a two
second delay, after which the lower readout will change to
‘
PASS’ indicating that access is now unlocked.
Note: A special case exists if the password has been set to
‘
0’. In this situation, access is permanently unlocked and
the lower readout will always show ‘
PASS’.
Press
to enter configuration.
(If an incorrect password has been entered and the
controller is still ‘locked’ then pressing
at this point
will take you to the ‘
Exit’ display with ‘no’ in the lower
readout. Simply press
to return to the ‘
ConF’
display.)
You will obtain the first display of configuration.
Conf
Conf
Conf
pass
inst
Conf