Thermcraft XST-6-0-36-3V User Manual
Page 114
Configuration
Installation and Operation Handbook
6-14
2408 and 2404 Controller
Name Description
Values
Meaning
AA
Alarm relay configuration
id
Identity
rELy
Relay output
Func
Function
nonE
No function
dIG
Digital output
SEnS
Digital output sense
nor
Normal (output energises when
TRUE, e.g. program events)
inv
Inverted (output de-energises when
TRUE, e.g. alarms)
The following digital events appear after ‘
SEnS’. Any one, or more, of the events can be
combined on to the output (see Fig. 6-2) by selecting ‘
YES’ in the lower readout.
1 - - -
Alarm 1 active
YES / no (- - -) = alarm type (e.g. FSL).
2 - - -
Alarm 2 active
YES / no If an alarm has not been configured
3 - - -
Alarm 3 active
YES / no in ‘AL ConF’ list, then display will
4 - - -
Alarm 4 active
YES / no differ:- e.g. Alarm 1 = ‘AL 1’.
mAn
Controller in manual mode
YES / no
Sbr
Sensor break
YES / no
SPAn
PV out of range
YES / no
Lbr
Loop break
YES / no
Ld.F
Load failure alarm
YES / no
tunE
Tuning in progress
YES / no
dc.F
Voltage output open circuit, or mA
output open circuit
YES / no
rmt.F
PDS module measurement
connection or remote input open
circuit
YES / no
iP1.F Input 1 failure
YES / no
nw.AL
New Alarm has occurred
YES / no
End
End of setpoint rate limit, or end
of program
YES / no
SYnc
Program Synchronisation active
YES / no
PrG.n
Programmer event output active,
where ‘n’ = event number from 1
to 8. (Not available with
8-segment programmer.)
YES / no
Figure 6-2 Combining several digital events on to one output
dIG
SEnS
nor
inv
Output
Module
Digital Events
OR