beautypg.com

Thermcraft XST-6-0-36-3V User Manual

Page 114

background image

Configuration

Installation and Operation Handbook

6-14

2408 and 2404 Controller

Name Description

Values

Meaning

AA

Alarm relay configuration

id

Identity

rELy

Relay output

Func

Function

nonE

No function

dIG

Digital output

SEnS

Digital output sense

nor

Normal (output energises when
TRUE, e.g. program events)

inv

Inverted (output de-energises when
TRUE, e.g. alarms)

The following digital events appear after

SEnS’. Any one, or more, of the events can be

combined on to the output (see Fig. 6-2) by selecting

YES’ in the lower readout.

1 - - -

Alarm 1 active

YES / no (- - -) = alarm type (e.g. FSL).

2 - - -

Alarm 2 active

YES / no If an alarm has not been configured

3 - - -

Alarm 3 active

YES / no in ‘AL ConF’ list, then display will

4 - - -

Alarm 4 active

YES / no differ:- e.g. Alarm 1 = ‘AL 1’.

mAn

Controller in manual mode

YES / no

Sbr

Sensor break

YES / no

SPAn

PV out of range

YES / no

Lbr

Loop break

YES / no

Ld.F

Load failure alarm

YES / no

tunE

Tuning in progress

YES / no

dc.F

Voltage output open circuit, or mA
output open circuit

YES / no

rmt.F

PDS module measurement
connection or remote input open
circuit

YES / no

iP1.F Input 1 failure

YES / no

nw.AL

New Alarm has occurred

YES / no

End

End of setpoint rate limit, or end
of program

YES / no

SYnc

Program Synchronisation active

YES / no

PrG.n

Programmer event output active,
where ‘n’ = event number from 1
to 8. (Not available with
8-segment programmer.)

YES / no

Figure 6-2 Combining several digital events on to one output

dIG

SEnS

nor

inv

Output

Module

Digital Events

OR

This manual is related to the following products: